Total connections required by the soft1 controller – Rockwell Automation 1789-L10_L30_L60 SoftLogix 5800 System User Manual User Manual
Page 229
Rockwell Automation Publication 1789-UM002J-EN-P - December 2012
229
Communicate with Devices on a ControlNet Network
Appendix B
Total Connections Required by the Soft1 Controller
This table calculates the connections used in this example.
The remote 1756-CNB and 1788-CNC card are configured as ‘none’ for the
communication format, so the SoftLogix controller would require a direct
connection for any I/O modules connected to these devices that you want in the
configuration for the SoftLogix controller.
Connection
Amount
Soft1 controller to 1784-PCICS card
0
Soft1 controller to remote 1756-CNB module
0
Soft1 controller to remote 1788-CNC card
0
Soft1 controller to remote PLC5C1
1
Connected, cached MSG from Soft1 to Control1
1
Connected, cached MSG from Soft1 to Flex1
1
Connected, cached MSG from Soft1 to PLC5C1
1
Produced TagA:
Produced from Soft1 to Control1
Consumed by PLC5C1
1
1
Consumed TagB from Control1
1
Total Connections Used: 7