Appendix F

Status Indicators

Controller Status Indicator and Display

Indicator

Status

Description

RUN

Off

The controller is in Program or Test mode.

Solid green

The controller is in Run mode.

I/O

Off

Either:
There are no devices in the I/O configuration of the controller.
The controller does not contain a project (controller memory is empty).

Solid green

The controller is communicating with all the devices in its I/O configuration.

Flashing green

One or more devices in the I/O configuration of the controller are not responding.

Flashing red

A virtual chassis error was detected. Contact your Rockwell Automation representative or local distributor.

FRC

Off

No tags contain I/O force values.
I/O forces are inactive (disabled).

Flashing green

At least one tag contains an I/O force value.
I/O force values are inactive (disabled).

Solid green

I/O forces are active (enabled).
I/O force values may or may not exist.

RS232

(1)

Off

No COM port was selected.

Solid green

The selected COM port was successfully assigned to channel 0 of the controller.

Solid red

There is a COM port conflict or you selected an invalid COM port number.

BAT

(1)

Off

Normal operation.

Flashing amber

The controller is in Power-up mode.

Solid red

Persistent storage for the controller has failed.

OK

Flashing red

If the controller is a new controller, then the controller requires a firmware update.
And the controller is not a new controller, then a major fault occurred.
To clear the fault, either:
Turn the keyswitch from PROG to RUN to PROG
Go online with RSLogix 5000 software

Solid red

The controller detected a non-recoverable fault, so it cleared the project from memory.
To recover, follow these steps.
1. Cycle power to the chassis.
2. Download the project.
3. Change to Run mode.
If the OK status indicator remains solid red, contact your Rockwell Automation representative or local distributor.

Solid green

The controller is OK.

(1) Note that these status indicators function slightly different than the same status indicators on a ControlLogix controller.