Example 4: Use the SoftLogix
Controller as a Gateway
The SoftLogix controller supports bridging over a ControlNet network. Any
SoftLogix MSG instruction that bridges one network has multiple pairs of
numbers in its communication path. To construct a communication path, follow
these steps.
1. Specify the port where the message exits.
2. Specify the next device.
3. Repeat
step 1
and
step 2
until you specify the target device.
For Port
Specify
Backplane port
1
DF1 port from the controller
2
ControlNet port from a communication card/module
Ethernet port from a communication card/module
DH+ port over channel A from a 1756-DHRIO module
DH+ port over channel B from a 1756-DHRIO module
3
For Device
Specify
ControlLogix backplane
Slot number
DF1 network
Station address (0…254)
ControlNet network
Node number (1…99 decimal)
DH+ network
Node number (1…77 decimal)
Ethernet network
IP address