Chapter 3

Communicate with Devices on an Ethernet Network

Ethernet I/O Data

I/O information is presented as a structure of multiple fields, which depend on
the specific features of the I/O module. The name of the structure is based on the
location of the I/O module in the system. Each I/O tag is automatically created
when you configure the I/O module through the programming software. Each
tag name follows this format:

Location:SlotNumber:Type.MemberName.SubMemberName.Bit

This address variable

Is

Location

Identifies network location
ADAPTER_NAME = identifies remote adapter or bridge

SlotNumber

Slot number of I/O module in its chassis

Type

Type of data
I = input
O = output
C = configuration
S = status

MemberName

Specific data from the I/O module; depends on the type of data the module can store.
For example, Data and Fault are possible fields of data for an I/O module. Data is the common name for values the are sent to or received
from I/O points.

SubMemberName

Specific data related to a MemberName.

Bit (optional)

Specific point on the I/O module; depends on the size of the I/O module (0…31 for a 32-point module)