Rockwell Automation 1789-L10_L30_L60 SoftLogix 5800 System User Manual User Manual

Page 62

Advertising
background image

62

Rockwell Automation Publication 1789-UM002J-EN-P - December 2012

Chapter 3

Communicate with Devices on an Ethernet Network

2. Enter tag configuration information.

3. Click Connection.

The Consumed Tag Connection dialog box appears.

4. Configure connection properties in the Consumed Tag Connection

dialog box.

5. Click OK when done.

Parameter

Description

Name

Enter the name of the tag.

Description

Enter a tag description.

Type Consumed.

Data Type

Enter the type of tag you want to create.

Scope

Consumed tags are always controller scope.

External Access

Select whether the tag has Read/Write, Read Only, or no access (None) from external applications such as HMIs.

Style

Choose the default style in which to display the value of the tag. The pull-down menu lists available display styles for the
chosen data type. Choose from Binary, Decimal, Hex, Octal, Date/Time, ASCII, Exponential, or Float.

Parameter

Description

Producer

Choose the name of the controller producing the data. The pull-down menu lists only those options that are available.

Remote Data

Enter the name of the tag in the remote controller that you want to consume.

RPI

Enter the requested packet interval. This is the amount of time (in ms) between updates of the data from the remote
controller. This is the minimum rate at which the local controller receives data. The valid RPI range for a Standard
consumed tag is 0.196…536870.911 ms. The valid RPI range for a Safety consumed tag is 1…500 ms and can only be
set on the Safety tab of the Consumed Tag Connection dialog box. Note that the Safety Tag RPI must match the rate
specified by Safety Task Period of the producing controller.
You must be offline or online in Program mode to change the RPI.