Appendix B

Communicate with Devices on a ControlNet Network

Consume a Tag from a PLC-5 Controller for the ControlNet Network

Complete these steps to consume a tag from a PLC-5 controller for the
controlNet network.

1. In RSNetWorx software, open the ControlNet configuration of the

PLC-5 controller and insert a Send Scheduled Message.

2. In RSLogix 5000 software, add the PLC-5 controller to the Controller

Organizer.

3. Create a user-defined data type that contains these members.

4. Create a consumed tag with the following properties.

5. In the RSNetWorx for ControlNet software, reschedule and save

the network.

Data Type

Description

DINT

Status

INT[x], where ’x’ is the output size of the data from the
PLC-5 controller
(If you are consuming only one INT, no dimension is
required)

Data produced by a PLC-5 controller

Tag Property

Type or Choose

Tag type

Consumed.

Controller

The PLC-5 for the ControlNet network that is producing the data.

Remote instance

The message number from the ControlNet configuration of the ControlNet
PLC-5 controller.

RPI

A power of two times the NUT of the ControlNet network. For example, if the NUT
is 5 ms, choose an RPI of 5, 10, 20, 40, and so forth.

Data type

The user-defined data type that you created.