Rockwell Automation Publication 1789-UM002J-EN-P - December 2012

93

Chapter

5

Configure and Use Simulated I/O

This chapter explains how to use SIM modules with a SoftLogix controller.

The 1789-SIM module is a software-only module that comes with the SoftLogix
controller; no hardware is required. You can put as many SIM modules as you
have available slots, on your system, according to your activation level.

The 1789-SIM module lets you change inputs and monitor outputs of your
application by toggling input bits and monitoring output bits on the 1789-SIM
module. You use this module to test logic without having physical I/O attached
to the system.

Configure Your System for a
1789-SIM Module

For the SoftLogix controller to simulate local I/O, you need the following:

A 1789-SIM module (comes with the SoftLogix 5800 controller)
Logix Designer application to configure the 1789-SIM module

You are limited by the activation level of your SoftLogix controller as to
how many modules you can install.

Even though the 1789-SIM module is a software-based module, each module you
create uses communication resources. If you are controlling actual I/O and
simulating I/O, the 1789-SIM module in your application use communication
resources that could impact control performance. If this occurs, increase the RPI
of your 1789-SIM module. This maintains control performance because the
greater RPI of the 1789-SIM module lessens the load on the SoftLogix system.

Topic

Page

Configure Your System for a 1789-SIM Module

93

Map I/O Data to the 1789-SIM Module

100

Toggle Inputs and Monitor Outputs

101

Example: Move Application Data into the 1789-SIM Tags

103