Total connections required by the soft1 controller, Example 3: softlogix controller to other devices – Rockwell Automation 1789-L10_L30_L60 SoftLogix 5800 System User Manual User Manual

Page 224

Advertising
background image

224

Rockwell Automation Publication 1789-UM002J-EN-P - December 2012

Appendix B

Communicate with Devices on a ControlNet Network

Each produced tag requires one connection for the producing controller
and an additional connection for each consuming controller. Each
consumed tag requires one connection.

Total Connections Required by the Soft1 Controller

This table calculates the connections used in this example.

Example 3: SoftLogix
Controller to Other Devices

This example, one SoftLogix controller communicates with other controllers
over the ControlNet network.

Connection

Amount

Soft1 controller to 1784-PCICS card

0

Soft1 controller to remote 1784-PCICS card

0

Connected, cached MSG from Soft1 to Soft2

1

Produced TagA

Produced from Soft1 to Soft2
Other consumer (2 are configured)

1
1

Consumed TagB

1

Total Connections Used: 4

3

2

1

4

5

Item

Description

1

ControlLogix controller (Control1)

2

ControlNet network

3

SoftLogix controller (Soft1)

4

PLC-5 controller (PLC5C1) for the ControlNet network

5

FlexLogix™ controller (Flex1)