Chapter 4
Programming the RediPANEL Modules

4–9

When using a PLC-2/20 or 2/30 with a RediPANEL module, the system must
include a 1772-SD2 Remote I/O Scanner/Distribution Panel (or a 1771-SN
Sub I/O Scanner Module). The 1772-SD2 allows the PLCs to communicate
with as many as 16 remote I/O devices in any configuration totaling 7 logical
racks of I/O or less.

For details on 1771-SD2 wiring connections and switch settings, see
Publication No. 1772-2.18 (The Remote I/O Scanner/Distribution Panel).

Programming Example

Switch Bank #1 on the RediPANEL Module is set to use:

Rack Address 2 (switch settings 1 - 6)

Module Group 0 (switch settings 7 and 8)

Figure 4.1 shows typical address instructions and how these instructions are
used in your PLC-2/20 or 2/30 program.

Figure 4.1
PLC-2/20 or 2/30 Programming Example

Input

Press Push
Button #1

Output

03

00

Push Button #4 Lamp

Push Button #1

Module Group 0

020

120

Module Group 0

Illuminate Push
Button #4

Rack #2

Bits

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

00

03

020

120

Using a PLC-2
with a 1772-SD2 Scanner