Using a plc-5 – Rockwell Automation 2705 RediPanel Push Button Module User Manual

Page 53

Advertising
background image

Chapter 4
Programming the RediPANEL Modules

4–14

The PLC-5/15 and 5/25 processors have built-in remote I/O scanners. No
additional hardware is required. Run the two conductor shielded cable (Blue
Hose) from the RediPANEL to the remote I/O port of the PLC-5.

To use the built-in scanner:

Set switch 8 in DIP Switch Bank SW-1 on the processor to the OPEN,
OFF or Scanner Mode position.

Set the baud rate on the RediPANEL module to 57.6K baud for a
PLC-5/15 or -5/25.

For an enhanced processor the baud rate can be 57.6K, 115.2K or 230.4K.

Programming Example

Switch Bank #1 on the RediPANEL Module is set to use:

Rack Address 3 (switch settings 1 - 6)

Module Group 4 (switch settings 7 and 8)

Figure 4.4 shows typical address instructions and how these instructions are
used in your PLC-5/15 or -5/25 program.

Figure 4.4
PLC–5/15, -5/25 Programming Example

Module Group 4

Output

Module Group 4

I: 034

O:034

01

01

Rack #3

Bits

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

04

05

06

07

10

11

12

13

14

15

16

17

00

01

02

03

Push Button #2 Lamp

Push Button #2

01

01

O:034

I: 034

Input

Using a PLC-5

Advertising