Chapter 4
Programming the RediPANEL Modules
4–25
The G File contains the configuration information for communications
between the RediPANEL module and the SLC 5/02.
•
Word 0 of the G File indicates the I/O mix of the scanner. You cannot
modify the contents of the G File’s word 0.
•
Word 1 of the G File defines the RIO rack address and starting group for
each network device.
•
Word 2 of the G File specifies the size of the network device.
You can only modify the contents of the G File in the offline mode. The file
is then downloaded to the SLC processor.
Example G File
0
6
4
6
4
0
0
2
0
4
6
2
0
2
2
0
0
0
Bit Number
0
1
0
0
0
0
0
0
0
1
0
0
0
0
0
I/O Mix, Word 0
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
1
6
4
0
1
1
1
0
0
1
1
0
0
0
0
1
1
1
1
1
1
0
0
1
1
0
0
1
Device Address, Word 1
Device Size, Word 2
RIO Rack 3
Staring
Group
RIO Rack 2
Staring
Group
RIO Rack 1
Staring
Group
RIO Rack 0
Staring
Group
(2) Quarter Rack devices, Starting Group 0 & 6
Full Rack Device, Starting Group 0
Half Rack Device, Starting Group 2
Three Quarter Rack Device, Starting Group 2
0
0
1
= 2219H
= E6F9H
Note: The 1747-SN Scanner does not support block transfer functions. Refer to scanner user manual
for additional information on scanner configuration.