Slc 5/02 programming example – Rockwell Automation 2705 RediPanel Push Button Module User Manual
Page 63
Advertising
![background image](/manuals/580444/63/background.png)
Chapter 4
Programming the RediPANEL Modules
4–24
The example in this section interfaces a RediPANEL module with an SLC
5/02 controller. An alarm, connected to an output module, signals when
communications with the RediPANEL are lost. The system consists of:
•
SLC 5/02 Processor (Catalog No. 1747-L524) in slot 0
•
Remote I/O Scanner (Catalog No. 1747-SN) in slot 1
•
Output Module (Catalog No. 1746-OB8) in slot 2
•
An alarm connected to the output module
•
Bulletin 2705 RediPANEL Module
Push Button Module
Alarm
RIO NETWORK
The 1747-SN Scanner can address four racks (0-3). 32 input words and 32
output words may be addressed in
1
/
4
,
1
/
2
,
3
/
4
, or full rack format. The
scanner module can connect to 16 Remote I/O devices.
SLC 5/02
Programming Example