Chapter 4
Programming the RediPANEL Modules

4–22

Figure 4.9 shows handshake timing diagrams. They are not precise timing
diagrams. Timing varies from application to application and is dependent
upon the number of remote I/O nodes, program scan time, etc.

Figure 4.9
Handshake Timing Diagrams

Push Button Input

Push Button Contact

Program Scan

Write to Outputs

Read Inputs

Handshake Output Bit 17

Handshake Input Bit 17

PLC Scan Cycle

Handshake holds the push button input high even if the push button contact signal goes low.