I/o complex equipment ‘ttmri, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual
Page 16
![background image](/manuals/581210/16/background.png)
Trusted
TM
TMR Module T8160
Issue 13 May 13
PD-T8160
16
4.1. I/O Complex Equipment ‘TTMRI’
Description:
Trusted
TM
TMR Interface to Regent equipment (simplex module).
OEM PARAMETERS
OEM parameter
Valid numbers
Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander Chassis)
The TICS chassis & slot number where the TMR Interface
module is placed. Chassis 1 is recommended for priority
operation.
CONFIGURATION
PHYSICAL MODULE:
RACK 1:
1 ANALOGUE Input
TMR Interface status. See "TMR Interface Status word format" in EXTRA
INFORMATION for description of data
RACK 2:
16 ANALOGUE Inputs
Each variable contains data on the transceivers connected to the TMR
Interface. Variable 1 is Regent chassis 1, Variable 16 is Regent chassis
16. See "Transceiver variable" in EXTRA INFORMATION for detailed
data structure.