4.14. I/O Complex Equipment ‘F7419’

Description:

T7419 Fire Detector Input Module. The Fire Detector Input Module occupies one slot
in the Regent+Plus I/O chassis and provides 16 line monitored input channels
designed to interface to remote fire input devices. This board definition will open a
single module. All inputs are presented in unpacked form (Boolean). Channel status
is, however, presented packed form. Each channel has a single bit of the variable.

Product Description reference: PD-T7032 Fire Detector Input Module

OEM PARAMETERS:

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed.

REGENT_CHASSIS
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O
where the Module is placed.

MONITOR_MASK

1 = mask fault LEDs
0 = enable fault LEDs

Entered as a 16 bit word. Bit 0 will mask channel 1, bit 15
will mask channel 16. This field will mask the
implementation of the fault LEDs on the module. Input
status is not affected.

OPEN_CURRENT

-2 to 24mA

Current at which to indicate failure at switch open. The data
is entered in the form of actual current, in milli Amps with
resolution of 1mA.

ON_OFF CURRENT

-2 to 24mA

Current at which to indicate a transition from Low/High or
High/Low has taken place. The data is entered in the form
of actual current, in milli Amps with resolution of 1mA.

SHORT_CURRENT

-2 to 24mA

Current at which to indicate failure at switch close. The data
is entered in the form of actual current, in milli Amps with
resolution of 1mA.

Advertising