Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual

Page 17

Advertising
background image

Trusted

TM

TMR Module T8160

Issue 13 May 13

PD-T8160

17

EXTRA INFORMATION

TMR Interface Status word format

Bit No.

Description

State

0

TMR Interface Slice A status

See TMR Interface Slice status information.

1

TMR Interface Slice A status

See TMR Interface Slice status information.

2

TMR Interface Slice B status

See TMR Interface Slice status information.

3

TMR Interface Slice B status

See TMR Interface Slice status information.

4

TMR Interface Slice C status

See TMR Interface Slice status information.

5

TMR Interface Slice C status

See TMR Interface Slice status information.

6

Not Used

7

Not Used

8

Not Used

9

Not Used

10

Not Used

11

Active/Standby

0 – Standby, 1 - Active

12

Educated

0 – uneducated, 1 - educated.

13

Impending Module

0 – ejectors open, 1 - ejectors closed

14

Module online

0 – TMR Interface offline, 1 - TMR Interface online

15

Permissible Slot

0 – Invalid Slot, 1 - Permitted

TMR Interface Slice status information.

Bit n+1

Bit n

State

0

0

Healthy slice

0

1

Transient fault

1

0

Hard fault

1

1

Unknown

Transceiver variable
Each of the 16 variables has the following configuration
Transceiver A

bits 0,1

Transceiver B

bits 2,3

Transceiver C

bits 4,5

Bit n+1

Bit n

State

0

0

Transceiver Healthy

0

1

Transceiver transient fault

1

0

Transceiver hard fault

1

1

Unknown

Notes:

1. All parameters must be supplied, even for virtual boards.

2. This module must appear before any attached Regent modules in the rack list.

3. The Permissible Slot status bit is 1 when the TMR Interface module has been correctly

configured in the I/O Connections and in the System Configuration Tool, even if the module is
not present.

4. If the Module On-line status bit is zero, the other status bits should not be used.