I/o complex equipment ‘sx7485, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual

Page 64

Advertising
background image

Trusted

TM

TMR Module T8160

Issue 13 May 13

PD-T8160

64

4.42. I/O Complex Equipment ‘SX7485’

Description:

T7485 Isolated Guarded Digital Output Module 24 to 120V ac/dc. The Isolated
Guarded Digital Output Module provides digitally switched outputs for controlling eight
field loads. The digital output circuits are ‘sourcing’ outputs that switch field power
ranging from 24 to 120V ac/dc. This board definition is used in a simplex
configuration.

Product Description reference: PD-T7034 Isolated Guarded Digital Output Module 24 to 120Vac/dc

OEM PARAMETERS:

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed

REGENT_CHASSIS
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

CONFIGURATION

PHYSICAL MODULE:

RACK 1:

8 BOOLEAN outputs

States to be written to the module identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 8 is module channel 8.
TRUE – channel high, FALSE – channel low

RACK 2:

1 BOOLEAN input

Input reflecting the board status of the module.
FALSE – board ok, TRUE – board fault

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

Advertising