I/o complex equipment ‘sx7441a, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual

Page 44

Advertising
background image

Trusted

TM

TMR Module T8160

Issue 13 May 13

PD-T8160

44

4.22. I/O Complex Equipment ‘SX7441A’

Description:

T7441A Digital Output Module, 24V dc. The Digital Output Module provides digitally
switched outputs for controlling 16 field loads. The 24V dc digital output circuits are
‘sourcing’ outputs that switch field power ranging from 18V dc to 32V dc. Field power
for the outputs is arranged in two isolated groups of 8 points. This board definition is
used in a simplex configuration.

Product Description reference: PD-T7015 DC Digital Output Module

OEM PARAMETERS:

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed

REGENT_CHASSIS
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

CONFIGURATION

PHYSICAL MODULE:

RACK 1:

16 BOOLEAN outputs

States to be written to the two modules identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 16 is module channel 16.
TRUE - channel high, FALSE – channel low

RACK 2:

1 BOOLEAN input

Input reflecting the board status of the two modules specified. FALSE -
board ok, TRUE – board fault

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

Advertising