PD-T8160

34

CONFIGURATION

PHYSICAL MODULE

RACK 1:

16 BOOLEAN inputs

Input states of the module as identified by the OEM parameters.

RACK 2:

1 ANALOGUE input

Channel Faults (1 bit per channel) for the module.
0 - channel ok, 1 - channel fault
(channel status will always be 0 for the ac version)

RACK 3:

1 BOOLEAN input

Input reflecting the board status of the module specified.
FALSE – board ok, TRUE – board fault

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

EXTRA INFORMATION

Entering the Threshold data:

At present the threshold values have to be entered as a count between 0 and 255, (8bit word), e.g. on
a 0VDC to 120 VDC system:

COUNTS = (( VOLTAGE + 5 ) / 37) * 255

55 V would be represented by:

55/120

=

0.458.

0.458 * 255

=

117 counts

The maximum count that can be entered is 16535, however the ISaGRAF kernel will limit any variable
to 240.