Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual
Page 34

Trusted
TM
TMR Module T8160
Issue 13 May 13
PD-T8160
34
CONFIGURATION
PHYSICAL MODULE
RACK 1:
16 BOOLEAN inputs
Input states of the module as identified by the OEM parameters.
RACK 2:
1 ANALOGUE input
Channel Faults (1 bit per channel) for the module.
0 - channel ok, 1 - channel fault
(channel status will always be 0 for the ac version)
RACK 3:
1 BOOLEAN input
Input reflecting the board status of the module specified.
FALSE – board ok, TRUE – board fault
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.
EXTRA INFORMATION
Entering the Threshold data:
At present the threshold values have to be entered as a count between 0 and 255, (8bit word), e.g. on
a 0VDC to 120 VDC system:
COUNTS = (( VOLTAGE + 5 ) / 37) * 255
55 V would be represented by:
55/120
=
0.458.
0.458 * 255
=
117 counts
The maximum count that can be entered is 16535, however the ISaGRAF kernel will limit any variable
to 240.