I/o complex equipment ‘dx7485, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual

Page 65

Advertising
background image

Trusted

TM

TMR Module T8160

Issue 13 May 13

PD-T8160

65

4.43. I/O Complex Equipment ‘DX7485’

Description:

T7485 Isolated Guarded Digital Output Module 24 to 120V ac/dc. The Isolated
Guarded Digital Output Module provides digitally switched outputs for controlling eight
field loads. The digital output circuits are ‘sourcing’ outputs that switch field power
ranging from 24 to 120V ac/dc. This board definition is used in a dual configuration.

Product Description reference: PD-T7034 Isolated Guarded Digital Output Module 24 to 120Vac/dc

OEM PARAMETERS:

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed

REGENT_CHASSIS
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
first Module is placed.

PARTNER_CHASSIS
PARTNER_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
second Module is placed.

CONFIGURATION

PHYSICAL MODULE:

RACK 1:

8 BOOLEAN outputs

States to be written to the module identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 8 is module channel 8.
TRUE – channel high, FALSE – channel low

RACK 2:

2 BOOLEAN input

Inputs reflecting the board status of the modules. Channel 1 is the first
module, channel 2 is the second module.
FALSE – board ok, TRUE – board fault

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

EXTRA INFORMATION

1. Writing to a channel of board 1 will cause physical writes to be made to both boards as

identified by the parameters associated with the board. Both boards must be managed by
the same TMR Interface.

Advertising