4.41. I/O Complex Equipment ‘DX7484_P’

Description:

T7484 Simplex Monitored Guarded Digital Output Module, 110V ac. The Monitored
Guarded Output Module provides switching of 90V ac to 130V ac power to 16 field
outputs. The outputs are arranged in two groups of 8 outputs, where each group is
powered from a common power source. This board definition is for a dual module
configuration, has packed channel status’ for each board and is recommended for use
with medium to high output count systems.

Product Description reference: PD-T7033 Monitored Guarded Output Modules

OEM PARAMETERS

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed

REGENT_CHASSIS
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O
where the first Module is placed.

PARTNER_CHASSIS
PARTNER_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O
where the second Module is placed

MONITER_MASK

1 = mask fault LEDs
0 = enable fault LEDs

First module fault LED mask. Entered as a 16 bit word. Bit
0 will mask channel 1,bit 15 will mask channel 16. This field
will mask the implementation of the fault LEDs on the
module. Input status is not affected.

FREQUENCY

0 – 1

Frequency of the module.
0 - 60Hz, 1 – 50Hz.

CONFIGURATION

PHYSICAL MODULE:

RACK 1:

16 BOOLEAN outputs

States to be written to the two modules identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 16 is module channel 16.
TRUE - channel high FALSE - channel low

RACK 2:

1 ANALOGUE input
Variable 1

Inputs reflecting the channel status of the first module of the two modules
specified. Bit 0 is the state of Channel 1, Bit 15 is the state of Channel 16.
0 - channel ok, 1 - channel fault

RACK 3:

1 ANALOGUE input
Variable 1

Inputs reflecting the channel status of the second module of the two
modules specified. Bit 0 is the state of Channel 1, Bit 15 is the state of
Channel 16.
0 - channel ok, 1 - channel fault

RACK 4:

2 BOOLEAN inputs

Inputs reflecting the board of the two modules specified. Channel 1 is he
state of the first module, Channel 2 is the state of the second FALSE –
board ok, TRUE - board fault

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

EXTRA INFORMATION

Writing to a channel of board 1 will cause physical writes to be made to both boards as identified by the
parameters associated with the board. Both boards must be managed by the same TMR Interface.