4.10. I/O Complex Equipment ‘DX7411F’

Description:

T7411F Monitored Digital Input Module, 24V dc. The Monitored Digital Input Module
interfaces to 16 field input devices. The Type F module connects to field inputs that
switch the ‘hot’ side of field power ranging from 15V dc to 80V dc. The module
performs complete testing of the input module electronics. This board definition is
used in a voted dual 2-oo-2 input configuration.

Product Description reference: PD-T7031 Monitored Digital Input Modules

OEM PARAMETERS:

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed

REGENT_CHASSIS
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O
where the first Module is placed.

PARTNER_CHASSIS
PARTNER_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O
where the second Module is placed

MONITER_MASK

1 = mask fault LEDs
0 = enable fault LEDs

Entered as a 16 bit word. Bit 0 will mask channel 1,bit 15 will
mask channel 16. This field will mask the implementation of
the fault LEDS on the module. Input status is not affected.

OPEN_VOLTAGE

0 – 240

Voltage at which to indicate failure at switch open. The data
is entered in the form of a decimal number in the range 0 -
255, however 240 is the maximum the user can enter to
accommodate test ranges within the module.

ON_OFF_VOLTAGE

0 – 240

Voltage at which to indicate a transition from Low/High or
High/Low has taken place. It is again entered as a decimal
value the range 0 - 255, however 240 is the maximum the
user can enter to accommodate test ranges within the
module.

SHORT_VOLTAGE

0 – 240

Voltage at which to indicate failure at switch close. The data
is entered in the form of a decimal number in the range 0 -
255, however 240 is the maximum the user can enter to
accommodate test ranges within the module.

MSEC

0 – any

This parameter is the number of milliseconds that the user
wishes to mask the error status bits in rack 1. This
accommodates the potential initial disagreement between
the two modules when a channel state changes.