I/o complex equipment ‘sx7446, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual

Page 47

Advertising
background image

Trusted

TM

TMR Module T8160

Issue 13 May 13

PD-T8160

47

4.25. I/O Complex Equipment ‘SX7446’

Description:

T7446 Relay Output Module. The Relay Output Module provides relay outputs for
controlling eight field loads. This board definition is used in a simplex configuration.

Product Description reference: PD-T7017 Relay Output Module

OEM PARAMETERS:

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed

REGENT_CHASSIS
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

CONFIGURATION

PHYSICAL MODULE:

RACK 1:

8 BOOLEAN outputs

States to be written to the two modules identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 8 is module channel 8.
TRUE - channel high, FALSE – channel low

RACK 2:

1 BOOLEAN input

Input reflecting the board status of the two modules specified.
FALSE - board ok, TRUE – board fault

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

Advertising