I/o complex equipment ‘dx7462, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual

Page 52

Advertising
background image

Trusted

TM

TMR Module T8160

Issue 13 May 13

PD-T8160

52

4.30. I/O Complex Equipment ‘DX7462’

Description:

T7462 DC Guarded Digital Output Module 48VDC. The DC Guarded Digital Output
Module provides digitally switched outputs for controlling eight field loads. Field power
for the outputs is arranged in two triplicated inputs. This board definition is used in a
dual configuration. . Each module can be in any Regent rack or slot. All data attached
to this definition is unpacked with BOOLEAN variables used.

Product Description reference: PD-7019 Regent+ Guarded 24, 48, 120Vdc.

OEM PARAMETERS:

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed

REGENT_CHASSIS
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

PARTNER_CHASSIS
PARTNER_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

CONFIGURATION

PHYSICAL MODULE:

2 (boards) x 8 output channels, Boolean, Dual

LOGICAL

RACK 1:

8 BOOLEAN outputs

States to be written to the two modules identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 8 is module channel 8.
TRUE - channel high, FALSE – channel low

RACK 2:

2 BOOLEAN inputs

Input reflecting the board status of the two modules specified.
Channel 1 is the state of the first module. Channel 2 is the state of the
second.
FALSE - board ok, TRUE – board fault

PROGRAMMING NOTE

Writing to a channel of board 1 will cause physical writes to be made to both boards as identified by the
parameters associated with the board. Both boards must be managed by the same TMR Interface
module.

Notes:

3. All parameters must be supplied, even for virtual boards.

4. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.