I/o complex equipment ‘sx7481_p, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual

Page 59

Advertising
background image

Trusted

TM

TMR Module T8160

Issue 13 May 13

PD-T8160

59

4.37. I/O Complex Equipment ‘SX7481_P’

Description:

T7481 Monitored Guarded Output Module, 24V dc. The Monitored Guarded Output
Module provides switching of 18V dc to 36V dc power to 16 field outputs. The outputs
are arranged in two groups of 8 outputs, where each group is powered from a common
power source. This board definition is for a simplex configuration, has packed channel
status’ for each board and is recommended for use with medium to high output count
systems.

Product Description reference: PD-T7033 Monitored Guarded Output Modules

OEM PARAMETERS

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed

REGENT_CHASSIS
REGENT_SLOT

1 - 16
1 - 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

MONITER_MASK

1 = mask fault LEDs
0 = enable fault
LEDs

Module fault LED mask. Entered as a 16 bit word. Bit 0 will
mask channel 1,bit 15 will mask channel 16. This field will mask
the implementation of the fault LEDs on the module. Input
status is not affected.

FREQUENCY

0 - 1

Frequency of the module.
0 - 60Hz, 1 - 50Hz.

CONFIGURATION

PHYSICAL MODULE:

RACK 1:

16 BOOLEAN outputs

States to be written to the module identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 16 is module channel 16.
TRUE – channel high, FALSE – channel low

RACK 2:

1 ANALOGUE input

Input reflecting the channel status of the module specified.
Bit 0 is the state of Channel 1, Bit 15 is the state of Channel 16
0 - channel ok, 1 – channel fault

RACK 3:

1 BOOLEAN input

Input reflecting the board status of the module specified.
FALSE – board ok, TRUE - board fault

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

Advertising