I/o complex equipment ‘tx7404, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual

Page 26

Advertising
background image

Trusted

TM

TMR Module T8160

Issue 13 May 13

PD-T8160

26

4.9. I/O Complex Equipment ‘TX7404’

Description:

T7404 AC Digital Input Module 110V ac. The AC Digital Input module provides input
sensing for 16 field input switches. The digital inputs are interfaced to the triplicated
I/O Safetybus. This board definition is used in a triplicated configuration. The inputs to
the modules are voted on a 2-oo-3 basis. The data presented is in unpacked form with
each discrepancy having a single BOOLEAN variable.

Product Description reference: PD-T7013 AC Digital Input Module 110V ac

OEM PARAMETERS:

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed

REGENT_CHASSIS
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

REGENT_CHASSIS 2
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

REGENT_CHASSIS 3
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

CONFIGURATION

PHYSICAL MODULE

RACK 1:

16 BOOLEAN Inputs

Voted data for input channels.
TRUE = channel high, FALSE = channel low

RACK 2:

3 BOOLEAN Inputs

Input reflecting the board status of the module specified.
First channel is board status for board 1
Second channel is board status for board 2
Third channel is board status for board 3
FALSE = board ok, TRUE = board fault.

RACK 3:

16 BOOLEAN Inputs

Data reflecting the discrepancy state of the last vote performed for the
channel.
Channel 1 contains data for module channel 1. Channel 16 contains
data for module channel 16.
TRUE = a discrepancy has occurred, FALSE = all channels agree. The
variable is not latched.

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

Advertising