4.19. I/O Complex Equipment ‘SX7431A’

Description:

T7431 Thermocouple Input Equipment. The thermocouple input equipment includes
a termination panel/multiplexer assembly and an input module that plugs into, and
interfaces with, a triplicated I/O Safetybus. The termination panel/multiplexer provides
connection points for 24 thermocouples and is cabled to the plug-in module. The
plug-in module provides 24 channel high noise immunity analogue to digital
conversion. This board definition is used in a simplex configuration. Input data is
unscaled.

Product Description reference: PD-T7024 Thermocouple Input Assembly

OEM PARAMETERS:

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed.

REGENT_CHASSIS
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

CONFIGURATION

PHYSICAL MODULE:

RACK 1:

24 ANALOGUE Inputs

Input channel states of module identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 24 is module channel 24.

RACK 2:

24 BOOLEAN Inputs

Channel range status. Channel 1 is module channel 1, Channel 24 is
module channel 24.
TRUE = channel is in range, FALSE = channel out of range.

RACK 3:

1 BOOLEAN input

Module status.
TRUE = Board fail, FALSE = board OK.

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

Advertising