I/o complex equipment ‘s7420_pp, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual

Page 39

Advertising
background image

Trusted

TM

TMR Module T8160

Issue 13 May 13

PD-T8160

39

4.17. I/O Complex Equipment ‘S7420_PP’

Description:

T7420A Analogue Input Module. The Analogue Input module provides high noise
immunity analogue to digital conversion of 8 differential or 16 single-ended field input
voltages or currents. The digitally converted values are interfaced to the triplicated I/O
Safetybus. This board definition is used in a simplex configuration, has packed
channel status’ for each board and is recommended for use with medium to high input
count systems.

Product Description reference: PD-T7023 Analogue Input Modules

OEM PARAMETERS:

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed.

REGENT_CHASSIS
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

CONFIGURATION

PHYSICAL MODULE:

RACK 1:
Variables 1- 16:

16 ANALOGUE Inputs

States to be written to the two modules identified by the OEM
parameters. Channel 1 is module channel 1 and Channel 16 is
module channel 16.

RACK 1:
Variable 17

1 ANALOGUE input

Range status.
Bit 0 is Channel 1, Bit 15 is Channel 16.
1 = channel is in range, 0 = channel is out of range.

RACK 1:
Variable 18

1 ANALOGUE input

Power status.
Bit 0 is Channel 1, Bit 15 is Channel 16.
1 = channel is ok, 0 = channel is faulted.

RACK 1:
Variable 19

1 ANALOGUE input

Module status on first bit of variable
1 = board fault, 0 = Board ok.

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

Advertising