I/o complex equipment ‘sx7462, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual

Page 51

Advertising
background image

Trusted

TM

TMR Module T8160

Issue 13 May 13

PD-T8160

51

4.29. I/O Complex Equipment ‘SX7462’

Description:

T7462 DC Guarded Digital Output Module 48VDC. The DC Guarded Digital Output
Module provides digitally switched outputs for controlling eight field loads. Field power
for the outputs is arranged in two triplicated inputs. This board definition is used in a
simplex configuration.

Product Description reference: PD-7019 Regent+ Guarded 24, 48, 120Vdc.

OEM PARAMETERS:

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed

REGENT_CHASSIS
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

CONFIGURATION

PHYSICAL MODULE:

1 (board) x 8 Output channels, BOOLEAN, Simplex

LOGICAL

RACK 1:

8 BOOLEAN outputs

States to be written to the module identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 8 is module channel 8.
TRUE – channel high, FALSE – channel low

RACK 2:

1 BOOLEAN input

Input reflecting the board status of the module.
FALSE – board ok, TRUE – board fault

Notes:

3. All parameters must be supplied, even for virtual boards.

4. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

Advertising