Trusted

TM

TMR Module T8160

Issue 13 May 13

PD-T8160

36

CONFIGURATION

PHYSICAL MODULE:

RACK 1:

16 BOOLEAN inputs

Input states of the module as identified by the OEM parameters.

RACK 2:

1 ANALOGUE input

Channel faults (I bit per channel) for the module.
0 – channel ok, 1 – channel fault

RACK 3

16 BOOLEAN outputs

These channels will force the input LEDs.
Channel 1 is module channel 1, Channel 16 is module channel 16.
Actual input via rack 1 is not affected.
TRUE – LED on, FALSE – LED off.
This function is called every time the board is scanned. Therefore
initialisation is needed at these outputs.

RACK 4

16 BOOLEAN outputs

These channels will rest the input of the relevant channel.
Channel 1 is module channel 1, Channel 16 is module channel 16.
TRUE – reset channel, FALSE – no reset. This function is called
every time the board is scanned. Therefore initialisation is needed
at these outputs.

RACK 5

1 BOOLEAN input

Input reflecting the board status of the module specified.
FALSE – board ok, TRUE – board fault.

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

EXTRA INFORMATION

The threshold settings are range checked in the ISaGRAF kernal and if they exceed the specified
limits, they are made to equal the maximum/minimum limit.