Trusted, Tmr module t8160, Configuration – Rockwell Automation T8160 Trusted TMR Interface User Manual
Page 32

Trusted
TM
TMR Module T8160
Issue 13 May 13
PD-T8160
32
CONFIGURATION
PHYSICAL MODULE
RACK 1:
16 BOOLEAN inputs
Input states of the module as identified by the OEM parameters.
RACK 2:
1 ANALOGUE input
Channel Faults (1 bit per channel) for the module.
0 - channel ok, 1 - channel fault
RACK 3:
1 BOOLEAN input
Input reflecting the board status of the module specified.
FALSE - board ok, TRUE – board fault
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.
3. The single analogue input channel returned provides the T7411F channel status in packed
notation. Channel 1 status will be in bit zero. Channel 16 status will be bit 15.
4. The single BOOLEAN input channel returned provides the T7411F board status.
EXTRA INFORMATION
Entering the Threshold data:
At present the threshold values have to be entered as a count between 0 and 255, (8bit word), e.g. on
a -5VDC to 32 VDC system:
COUNTS = (( VOLTAGE + 5 ) / 37) * 255
16 V would be represented by:
(16+5)/37
=
0.567.
0.567 * 255
=
145 counts
0VDC would be represented by:
(0+5)/37
=
0.135
0.135 * 255
=
34 counts