Trusted, Tmr module t8160, Configuration – Rockwell Automation T8160 Trusted TMR Interface User Manual

Page 32

Advertising
background image

Trusted

TM

TMR Module T8160

Issue 13 May 13

PD-T8160

32

CONFIGURATION

PHYSICAL MODULE

RACK 1:

16 BOOLEAN inputs

Input states of the module as identified by the OEM parameters.

RACK 2:

1 ANALOGUE input

Channel Faults (1 bit per channel) for the module.
0 - channel ok, 1 - channel fault

RACK 3:

1 BOOLEAN input

Input reflecting the board status of the module specified.
FALSE - board ok, TRUE – board fault

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

3. The single analogue input channel returned provides the T7411F channel status in packed

notation. Channel 1 status will be in bit zero. Channel 16 status will be bit 15.

4. The single BOOLEAN input channel returned provides the T7411F board status.

EXTRA INFORMATION

Entering the Threshold data:

At present the threshold values have to be entered as a count between 0 and 255, (8bit word), e.g. on
a -5VDC to 32 VDC system:

COUNTS = (( VOLTAGE + 5 ) / 37) * 255

16 V would be represented by:

(16+5)/37

=

0.567.

0.567 * 255

=

145 counts

0VDC would be represented by:

(0+5)/37

=

0.135

0.135 * 255

=

34 counts

Advertising