Trusted

TM

TMR Module T8160

Issue 13 May 13

PD-T8160

28

CONFIGURATION

PHYSICAL MODULE:

RACK 1:

16 BOOLEAN inputs.

Voted states of the two 7411F boards as identified by the OEM
parameters.

RACK 2:

3 ANALOGUE inputs

Channel 1 – Error status. i.e. 1 bit per pair of channels. LSB = first

channel. This is set when the corresponding channels of the
two boards disagree after the number of milliseconds
configured in the OEM parameter MSEC.

Channel 2 – Channel Faults (1 bit per channel) for the first module of the

pair. 1 – channel ok, 0 - channel fault

Channel 3 – Channel Faults (1 bit per channel) for the second module of

the pair. 1 - channel ok, 0 - channel fault

RACK 3:

2 BOOLEAN inputs

Inputs reflecting the board status of the two 7411F boards specified.
Channel 1 is module 1 and Channel 2 is module 2. FALSE - board ok,
TRUE - board fault

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

EXTRA INFORMATION

Error status:

The error status bits are only set IF channels disagree AND each channel is NOT in a
channel fault condition after MSEC has been exceeded.

The algorithm for the calculation of the error bits is:

Channel state

Channel state

Channel Fault

Channel Fault

Voted input

Error bit

Board 1

Board 2

Board 1

Board 2

After MSEC

Exceeded

Low

Low

In range

In range

Low

0

Low

Low

In range

Fault

Low

0

Low

Low

Fault

In range

Low

0

Low

Low

Fault

Fault

Low

0

Low

High

In range

In range

High

1

Low

High

In range

Fault

Low

0

Low

High

Fault

In range

High

0

Low

High

Fault

Fault

High

1

High

Low

In range

In range

High

1

High

Low

In range

Fault

High

0

High

Low

Fault

In range

Low

0

High

Low

Fault

Fault

High

1

High

High

In range

In range

High

0

High

High

In range

Fault

High

0

High

High

Fault

In range

High

0

High

High

Fault

Fault

Low

0

Entering the Threshold data:

At present the threshold values have to be entered as a count between 0 and 255, (8bit word), e.g. on
a -5V dc to 32V dc system:

COUNTS = (( VOLTAGE + 5 ) / 37) * 255

16V would be represented by:

(16+5)/37

=

0.567.

0.567 * 255

=

145 counts

0VDC would be represented by:

(0+5)/37

=

0.135

0.135 * 255

=

34 counts