I/o complex equipment ‘sx7420d, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual

Page 38

Advertising
background image

Trusted

TM

TMR Module T8160

Issue 13 May 13

PD-T8160

38

4.16. I/O Complex Equipment ‘SX7420D’

Description:

T7420A Analogue Input Module. The Analogue Input module provides high noise
immunity analogue to digital conversion of 8 differential or 16 single-ended field input
voltages or currents. The digitally converted values are interfaced to the triplicated I/O
Safetybus. This board definition is for differential inputs and is used in a simplex
configuration.

Product Description reference: PD-T7023 Analogue Input Modules

OEM PARAMETERS:

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed

REGENT_CHASSIS
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

CONFIGURATION

PHYSICAL MODULE

RACK 1:

8 ANALOGUE Inputs

Input channel states of module identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 8 is module channel 8.

RACK 2:

8 BOOLEAN Inputs

Channel range status. Channel 1 is module channel 1, Channel 8 is
module channel 8.
TRUE = channel is in range, FALSE = channel out of range.

RACK 3:

16 BOOLEAN Inputs

Channel power status. Channel 1 is module channel 1, Channel 8 is
module channel 8.
TRUE = channel OK, FALSE = channel fault.

RACK 4:

1 BOOLEAN input

Module status. TRUE = Board fail, FALSE = board OK.

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

Advertising