I/o complex equipment ‘sx7484, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual

Page 60

Advertising
background image

Trusted

TM

TMR Module T8160

Issue 13 May 13

PD-T8160

60

4.38. I/O Complex Equipment ‘SX7484’

Description:

T7484 Simplex Monitored Guarded Digital Output Module, 110V ac. The Monitored
Guarded Output Module provides switching of 90V ac to 130V ac power to 16 field
outputs. The outputs are arranged in two groups of 8 outputs, where each group is
powered from a common power source. This board definition is for a simplex
configuration.

Product Description reference: PD-T7033 Monitored Guarded Output Modules

OEM PARAMETERS

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed

REGENT_CHASSIS
REGENT_SLOT

1 - 16
1 - 10

The chassis & slot number within the Regent+Plus I/O where
the Module is placed.

MONITER_MASK

1 = mask fault LEDs
0 = enable fault LEDs

Module fault LED mask. Entered as a 16 bit word. Bit 0 will
mask channel 1,bit 15 will mask channel 16. This field will
mask the implementation of the fault LEDs on the module.
Input status is not affected.

FREQUENCY

0 - 1

Frequency of the module.
0 – 60Hz, 1 – 50Hz.

CONFIGURATION

PHYSICAL MODULE:

RACK 1:

16 BOOLEAN outputs

States to be written to the module identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 16 is module channel 16.
TRUE – channel high, FALSE – channel low

RACK 2:

16 BOOLEAN inputs

Inputs reflecting the channel status of the module specified.
Bit 0 is the state of Channel 1, Bit 15 is the state of Channel 16.
FALSE – channel ok, TRUE – channel fault

RACK 3:

1 BOOLEAN input

Input reflecting the board status of the module specified
FALSE – board ok, TRUE - board fault

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.