4.33. I/O Complex Equipment ‘SX7480’

Description:

T7480 Guarded Analogue Output Module. The Guarded Analogue Output Module
provides six 4mA - 20mA current output sources for driving user loads. The outputs
are 12-bit D-to-A converted values driven from a triplicated I/O Safetybus interface.
The module requires external power from a nominal 24V dc field power source to
power the optically isolated analogue field-side circuits. This board definition is for a
simplex configuration.

Product Description reference: PD-T7026 Guarded Analogue Output module

OEM PARAMETERS:

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed

REGENT_CHASSIS
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

CONFIGURATION

PHYSICAL MODULE:

RACK 1:

6 ANALOGUE outputs

States to be written to the two modules identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 6 is module channel 6.

RACK 2:

1 BOOLEAN inputs

Module status.
FALSE – board ok, TRUE - board fault

Notes: