4.46. I/O Complex Equipment ‘M7491’

Description:

T7491 Multiplexed I/O Module. The Multiplexed I/O Module occupies one slot in the
Regent+Plus I/O chassis and provides two serial communications port interfaces to
remote multiplexed digital I/O and addressable loop devices. The module provides an
economical interface to inputs and outputs for matrix and mimic displays in fire and
gas systems. Other applications include remote digital I/O and addressable loop
devices (fire detectors). The serial communications support connection to equipment
in the MIU and FGS product ranges.

Product Description reference: PD-T7035 Multiplexed I/O Module

OEM PARAMETERS:

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface module
is placed.

REGENT_CHASSIS
REGENT_SLOT

1 - 16
1 - 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

MD0-MD7

0 - 2

This implementation allows up to eight Matrix drivers to be
attached to this module. MDn defines which Communication link
is to be used for each particular matrix driver.

0 = Present
1 = Port 1
2 = Port 2

CONFIGURATION

PHYSICAL MODULE:

RACK 1:

1 BOOLEAN input

Input reflecting the board status of the module specified
FALSE - board ok, TRUE – board fault

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

3. The single input channel returned provides the T7491 board status.

4. This module MUST appear in the I/O configuration BEFORE the associated M7491_I(P) and

M7491_O(P) modules.