4.3. I/O Complex Equipment ‘SX7401’

Description:

T7401 DC Digital Input Module, 24V dc. The Digital Input Module interfaces 16
discrete field devices into a triplicated I/O Safetybus. Field power for the input is
arranged in two 8-point groups. The 24V dc digital input module provides 16 sinking
input circuits capable of sensing digital inputs that switch field power ranging from
14V dc to 32V dc. This board definition is for a module used in a simplex
configuration.

Product Description reference: PD-T7011 DC Digital Input Modules

OEM PARAMETERS

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed.

REGENT_CHASSIS
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

CONFIGURATION

16 input channels, Boolean, simplex 1 status channel Boolean

PHYSICAL

1 (board) X 16 input channels, Boolean, simplex.

LOGICAL

RACK 1:

16 BOOLEAN inputs

States of the module channel inputs identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 16 is module channel 16.
TRUE - channel high, FALSE - channel low

RACK 2:

1 BOOLEAN input

Input reflecting the board status of the module specified.
FALSE - board OK, TRUE – board fault.

Note: Board channels are numbered 1 (LSB = bit 0) to 16 (MSB = bit 15).

PROGRAMMING NOTE

All channels for both real and virtual boards MUST have a variable attached regardless.

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.