I/o complex equipment ‘dx7464, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual

Page 54

Advertising
background image

Trusted

TM

TMR Module T8160

Issue 13 May 13

PD-T8160

54

4.32. I/O Complex Equipment ‘DX7464’

Description:

T7464 AC Guarded Digital Output Module 110V ac. The AC Guarded Digital Output
Module provides digitally switched outputs for controlling 16 field loads. The 110V ac
digital output circuits are ‘sourcing’ outputs that switch field power ranging from 90V ac
to 130V ac. Field power for the outputs is arranged in two isolated groups of 8 points.
This board definition is used in a dual configuration. Each module can be in any
Regent rack or slot. All data attached to this definition is unpacked with BOOLEAN
variables used.

Product Description reference: PD-T7021 AC Guarded Digital Output Module 110V ac

OEM PARAMETERS:

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface
module is placed

REGENT_CHASSIS
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

PARTNER_CHASSIS
PARTNER_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
Module is placed.

CONFIGURATION

PHYSICAL MODULE:

RACK 1:

16 BOOLEAN outputs

States to be written to the two modules identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 16 is module channel 16.
TRUE - channel high, FALSE – channel low

RACK 2:

2 BOOLEAN inputs

Input reflecting the board status of the two modules specified.
Channel 1 is the state of the first module. Channel 2 is the state of the
second.
FALSE - board ok, TRUE – board fault

PROGRAMMING NOTE

Writing to a channel of board 1 will cause physical writes to be made to both boards as identified by the
parameters associated with the board. Both boards must be managed by the same TMR Interface
module.

Notes:

5. All parameters must be supplied, even for virtual boards.

6. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

Advertising