4.4. I/O Complex Equipment ‘TX7401’

Description:

T7401 DC Digital Input Module, 24V dc. The Digital Input Module interfaces 16
discrete field devices into a triplicated I/O Safetybus. Field power for the input is
arranged in two 8-point groups. The 24V dc digital input module provides 16 sinking
input circuits capable of sensing digital inputs that switch field power ranging from
14V dc to 32V dc. This board definition is for modules used in a triplicated
configuration.

Product Description reference: PD-T7011 DC Digital Input Modules

OEM PARAMETERS

OEM parameter

Valid numbers

Description

TICS_CHASSIS
TICS_SLOT

1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)

The TICS chassis & slot number where the TMR Interface is
placed.

REGENT_CHASSIS
REGENT_SLOT

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
first Module is placed.

REG_CHASSIS2
REG_SLOT2

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
second Module is placed.

REG_CHASSIS3
REG_SLOT3

1 – 16
1 – 10

The chassis & slot number within the Regent+Plus I/O where the
third Module is placed.

CONFIGURATION

PHYSICAL

3 (boards) X 16 digital input channels, Boolean, triplex.

LOGICAL

RACK 1:

16 BOOLEAN inputs

Voted data for input channels
TRUE – channel high, FALSE - channel low

RACK 2:

3 BOOLEAN inputs

Input reflecting the board status of the module specified.
First channel is board status for board 1.
Second channel is board status for board 2.
Third channel is board status for board 3.
FALSE – board ok, TRUE - board fault.

RACK 3:

16 BOOLEAN inputs

Data reflecting the discrepancy status of the last vote performed for the
channel
Channel 1 contains data for module channel 1, Channel 16 contains
data for module channel 16.
TRUE - A discrepancy has occurred, FALSE - All channels agree. The
variable is not latched.

Note: The value will be TRUE if any of the channels is different to the others. i.e. a discrepancy is

present. The discrepancy value is not latched or filtered in any way.

PROGRAMMING NOTE

ALL channels for both real and virtual boards MUST have a variable attached regardless. Assign the
same CHASSIS/SLOT user parameter values to each board as allocated.

Notes:

1. All parameters must be supplied, even for virtual boards.

2. Trusted

TM

chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers

start at 1.

Advertising