Tweco 400 Ultra-Cut(May 2014) User Manual
Page 17
ULTRA-CUT 100 XT/200 XT/300 XT/400 XT
Manual 0-5302
SPECIFICATIONS
2-3
Ultra-Cut 100 XT™ Power Supply
Input
Power Input
Current
Suggested Sizes (See Note)
Voltage
Freq.
3-Ph
3-Ph
Fuse (Amps) Wire (AWG)
Wire (mm
2
)
(Volts)
(Hz)
(kVA)
(Amps)
3-Ph
3-Ph
3-Ph
400
50/60
21
31
40-45
#12
4
Ultra-Cut 200 XT™ Power Supply
Input
Power Input
Current
Suggested Sizes (See Note)
Voltage
Freq.
3-Ph
3-Ph
Fuse (Amps)
Wire (AWG) Wire (mm
2
)
(Volts)
(Hz)
(kVA)
(Amps)
3-Ph
3-Ph
3-Ph
400
50/60
42
62
100
#6
16
Ultra-Cut 300 XT™ Power Supply
Input
Power Input
Current
Suggested Sizes (See Note)
Voltage
Freq.
3-Ph
3-Ph
Fuse (Amps) Wire (AWG) Wire (mm
2
)
(Volts)
(Hz)
(kVA)
(Amps)
3-Ph
3-Ph
3-Ph
400
50/60
63
93
150
#4
25
IEC
400
50/60
72
106
150
#4
25
Ultra-Cut 400 XT™ Power Supply
Input
Power Input Current
Suggested Sizes (See Note)
Voltage
Freq.
3-Ph
3-Ph
Fuse (Amps)
Wire (AWG) Wire (mm
2
)
(Volts)
(Hz)
(kVA)
(Amps)
3-Ph
3-Ph
3-Ph
400
50/60
93
137
200
#1
50
NOTE
* Suggested wire size based on United States NFPA 70 National Electrical Code 2011 edition published by the Na-
tional Fire Prevention Association. Listings are from table 400.5(A)(2) for flexible cord of certain types rated for 75
deg C in ambient temperatures up to 30 deg C. Using wires of lower temperature rating or different insulation type
may require larger wire size. De rate for higher ambient.
These are suggestions only. Always refer to your local and national codes that apply to your region for final deter-
mination of correct wire type and size.