Tweco 400 Ultra-Cut(May 2014) User Manual

Page 205

Advertising
background image

ULTRA-CUT 100 XT/200 XT/300 XT/400 XT

Manual 0-5302

APPENDIX

A-77

5. If TS2 is within the correct range the problem may be with the Relay board or the CCM.

a. The output from the relay board going to the CCM is on pin 30 of the 40 pin ribbon cable (J4 of Relay board to J23

of the CCM I/O board). It is an analog voltage that should range between 0.44V at 0 deg C to 1.6V at 40C. If it is

confirmed that the room ambient is not above 40C and Ambient temperature signal at pin 30 is higher than 1.6V then

the Relay board is defective.

b. If Ambient temperature signal at pin 30 is OK, less than 1.6V, and the room ambient is not above 40C then the CCM

is bad.

265-270 Inverter No Input Power

There are several digital signals on the ribbon cables between the inverter sections and the CCM that involve some level of

voltage. These include AC_INPUT_FLT\, INVERTER _FLT\, OVERTEMP_FLT\ and POWER_PRESENT. Normally all of these

should be high. Before power is applied to the inverter modules the CCM has already performed a continuity check to see if

that section is in place and it’s ribbon cable connected (code 224 & 237). As soon as power is applied to the inverter modules

the CCM checks these 4 signals and, having already confirmed there is an inverter whose ribbon cable is connected. If it

finds none of the signals have voltage, it assumes there is no power into the section or something is wrong with that inverter

section’s bias power.

Possible causes:

• The 3 input phases, J103-105 to that inverter section not connected.
• The circuit breaker CB2 providing the 120 VAC to the contactor (and Remote Arc Starter) has tripped.
• The contactor powering that section (and others) defective.
• Relay board defective.
• Inverter defective.
• CCM defective.

Troubleshooting:

1. Check that the input power cables are connected to the inverters.

2. Check if the contactor for that section (W1 for 1A, 1B, 2A; W2 for 2B, 3A, 3B) is energized.

a. There is a rectangular section in the middle of each contactor top that can be used to attach auxiliary contacts. This

can also be an indicator of contactor operation as it pulls in when the contactor is energized.

b. Check for CB2 on the rear panel being tripped. The white button marked “5” indicating it’s 5 amps, will pop out if

tripped. Reset it and if it pops out again something (contactor coil?) may be shorted.

c. Measure for 120 VAC on the contactor coil. If present, but the contactor isn’t pulled in, it’s probably a defective

contactor.

3. On the Relay board D22, CONTACTOR ON LED (green) next to relay K1 lights if K1 is being told to energize.

a. If it’s on check for 120 VAC between J8-1 and J8-9. If present the relay board is OK.

b. If D22 is on but 120 VAC is not present at J8-1 and J8-9 (make sure meter is set for ACV) then the relay board is

defective.

c. D22 is not on, go to the 40 pin ribbon cable test connector and measure voltage on pin 17 (relative to TP1 on either

the Relay board or the CCM I/O Board). It should be low, less than 1 volt. If it is the relay board is likely bad. If it’s

high, about 24VDC then the CCM may be bad, not telling the contactor to turn on.

4. The inverter section may be defective with a bad bias supply. Swap the inverter end of the ribbon cable with one next to

it.

a. If it now reports a different code, that of the inverter that was swapped with, then the original section is bad.

b. If it still reports the same section even though the ribbon cable was swapped then the CCM is bad.

Advertising
This manual is related to the following products: