ULTRA-CUT 100 XT/200 XT/300 XT/400 XT

Manual 0-5302

APPENDIX

A-71

Additional hint: Inverter control PCBs have a green LED, D24, PWM ON, that lights when that section is enabled and has a

demand signal. The LED brightness is relative to the output so may be very dim if output is low. If that LED doesn’t light

may indicate a defective inverter (control board).

224

Inverter 1 not found.

There must be an inverter connected in the 1st section, 1A, to be able to pilot. During the power up sequence, before power

is connected to the inverters, the CCM does a continuity test to see if its section 1A ribbon cable (J31 on CCM) is connected.

Causes & troubleshooting:

• As this is just a continuity test it is very unlikely to be a bad inverter. Most likely a poor connection or defective ribbon

cable.

o Check ribbon cable connections at both ends of INV1A to CCM J31 (1A) cable. Make sure it is plugged into J31,

the top connector, on the CCM.

o Plug a different inverter cable into J31, doesn’t matter which one for this test as long as it’s plugged into an inverter

on the other end. If still gives 224, “Inverter 1 not found” fault, it’s a bad CCM. Otherwise it’s the ribbon cable.

225-230 Inverter Revision and CCM incompatible.

If sometime in the future we should make a change to the inverter making it incompatible with older CCM we have included

a hardware key that would change to indicate this. During the power up sequence, before power is connected to the invert-

ers, the CCM does a continuity test to determine what is the hardware key configuration. The key uses 3 lines of the CCM to

inverter ribbon cable which are named IS_ID_A, IS_ID_B, IS_ID_C (on pins 12, 13 & 14) and checks for continuity to a 4th

line OUTCOM (pin 9). The test consists of applying voltage to OUTCOM and looking for that voltage coming back on the 3

ID pins. The present configuration has all 3 lines connected to OUTCOM so all 3 should be high.

To get the 225-230 code now when we don’t have any incompatible revisions would most likely be a bad connection in the

ribbon cable between the CCM and the inverter or a defective CCM (unlikely).

• On the inverter section swap the ribbon cable with that of a different inverter section. If fault remains unchanged, still

calls out the original inverter section, the problem is with either ribbon cable or CCM.

• On the inverter end put the ribbon cables back in their original positions. Now swap suspect ribbon cable with another

one on the CCM. If the fault now moves to a different section it’s the ribbon cable. If it remains with the original sec-

tion the problem is the CCM.

231-236 Inverter VAC Mismatch.

Different inverter modules are manufactured for 480VAC, 380-415VAC & 208-230VAC operation voltages. There is a key,

called inverter ID, read through the inverter’s ribbon cable, to identify which voltage range the inverter is designed for. The

unit itself is wired differently for the different input voltages and part of that includes a jumper at J61 on the System Bias

board that indicates to the System Bias board what voltage the unit is wired to accept.

At power on, the System Bias board measures the incoming voltage, determines what input voltage range it fall into and

sends that range information to the CCM. Before Appling power to the inverters by turning on the input contactors, the CCM

checks that each connected inverter is of the correct voltage matching that of the System Bias board. The inverter ID’s are

read from the lowest section to the highest so in all cases if it truly is a wrong voltage inverter it should call out the A section

whose code is read first. A VAC mismatch of a B section is likely another problem.

Possible causes:

• Wrong voltage inverter (very unlikely but easy to check).
• System Bias board wrong J61 jumper (unlikely but easy to check)
• Defective inverter.
• Ribbon Cable
• CCM
• System Bias board defective.