Troubleshooting:

1. If both D2 and D3 are on and you still have 101 fault replace the CCM. Otherwise go to step 2 except if it’s an AC 200

XT skip to step 4.

2. If D3 is not on and there is a TSC 3000 in use remove its cable from J54. K7 on the Relay board will de-energize and

satisfy the Plasma Enable to K1. If D3 is now on problem was in the TSC 3000 or its cable. Otherwise reconnect the

cable.

3. For an Ultra-Cut with DFC 3000 or GCM 2010 or an Auto-Cut 300 with a GCM 1000 XT remove the cable from J55

the gas control connector and jumper pins 1 & 2. If D3 is on now problem is in the Gas Control or its cable. If D3

still not on replace the Gas Control cable.

4. If neither of the above steps works, on the CCM I/O board, jumper J26-7 to GND (TP1 on I/O). If D2 is on and D3

still does not light then replace the CCM.

5. If D3 does light in the above step find the 40 pin ribbon cable plugged in to the top of the CCM. Confirm that it is

plugged in to both the CCM and the Relay board and the connector tabs are locked in place. Now using the spare

receptacle measure voltage between GND (TP1 on I/O) and the ribbon cable pin 12. It should be zero V. If not, if it’s

something like 10-15VDC, the ribbon cable is open or the Relay board is defective.

1

2

4

5

E-STOP

K?

GREEN

D13

(59)

12

15

13

16

J5

1A

F20

16

14

13

15

J56

(57)

(56)

(58)

16

14

17

15

J55

GAS

CONTROL

CABLE

3

4

J26

AC24V GCM1

15

7

J10

AC24V Ret - GCM1

(114)

K1

PLASMA ENABLE

(112)

CCM I/O BOARD

RELAY BOARD

(103)

(110)

GCM 2010 GAS CONTROL

XT PLASMA SUPPLY

GCM 2010 CONTROL BOARD

GCM 2010 PLASMA ENABLE / E-STOP SIMPLIFIED CIRCUIT

Art # 12306

102

Pilot Ignition Failure

Code 102 is activated when there is no pilot current after 15 seconds of firing the Arc Starter. Pilot ignition requires the Pilot

board to be enabled, pilot switch (IGBT) turned on and high voltage pulses (HF) from the arc Starter (either the Remote Arc

Starter RAS 1000 XT or GCM 1000 XT or the arc starter built in to the AC 200 XT) applied between the tip and the electrode

of the torch.

Possible Causes for 102 code:

• No HF to the torch due to broken pilot wire connection in the torch leads.
• No HF to the torch due to defective Arc Starter.
• Arc Starter not receiving power.
• Pilot board not enabled.
• Pilot board defective.
• Relay board defective.
• Work lead current sensor defective.
• CCM defective.