INSTALLATION

3-1

SECTION 3: INSTALLATION

3.01 Installation Requirements

Electric Supply

The electrical supply network, the gas and water supply system must meet local safety standards. This conformity shall be

checked by qualified personnel.

Ultra-Cut 100 XT™ Power Supply

Input

Power Input

Current

Suggested Sizes (See Note)

Voltage

Freq.

3-Ph

3-Ph

Fuse (Amps) Wire (AWG)

Wire (mm

2

)

(Volts)

(Hz)

(kVA)

(Amps)

3-Ph

3-Ph

3-Ph

400

50/60

21

31

40-45

#12

4

Ultra-Cut 200 XT™ Power Supply

Input

Power Input

Current

Suggested Sizes (See Note)

Voltage

Freq.

3-Ph

3-Ph

Fuse (Amps)

Wire (AWG) Wire (mm

2

)

(Volts)

(Hz)

(kVA)

(Amps)

3-Ph

3-Ph

3-Ph

400

50/60

42

62

100

#6

16

Ultra-Cut 300 XT™ Power Supply

Input

Power Input

Current

Suggested Sizes (See Note)

Voltage

Freq.

3-Ph

3-Ph

Fuse (Amps) Wire (AWG)

Wire

(mm

2

)

(Volts)

(Hz)

(kVA)

(Amps)

3-Ph

3-Ph

3-Ph

400

50/60

63

93

150

#4

25

IEC

400

50/60

72

106

150

#4

25

Ultra-Cut 400 XT™ Power Supply

Input

Power Input Current

Suggested Sizes (See Note)

Voltage

Freq.

3-Ph

3-Ph

Fuse (Amps)

Wire (AWG) Wire (mm

2

)

(Volts)

(Hz)

(kVA)

(Amps)

3-Ph

3-Ph

3-Ph

400

50/60

93

137

200

#1

50

NOTE

* Suggested wire size based on United States NFPA 70 National Electrical Code 2011 edition published by the

National Fire Prevention Association. Listings are from table 400.5(A)(2) for flexible cord of certain types rated for

75 deg C in ambient temperatures up to 30 deg C. Using wires of lower temperature rating or different insulation

type may require larger wire size. Derate for higher ambient.

These are suggestions only. Always refer to your local and national codes that apply to your region for final deter-

mination of correct wire type and size.

Gas Supply

The customer must supply all gases and pressure regulators. Gases must be of high quality. Pressure regulators must be double-

stage and installed as close as possible to the gas console. Contaminated gas can cause one or more of the following problems:

• Reduced cutting speed
• Poor cut quality
• Poor cutting precision
• Reduced consumables life.
• Oil or grease contamination from compressed or bottled air can cause fires in conjunction with oxygen.