Tweco 400 Ultra-Cut(May 2014) User Manual

Page 204

Advertising
background image

ULTRA-CUT 100 XT/200 XT/300 XT/400 XT

A-76

APPENDIX

Manual 0-5302

Possible causes:

• Cooling fan(s) not operating.
• Disrupted air flow.
• Defective inverter module.
• Inverter Ribbon cable bad connection.
• Defective CCM.

Originally 100 and 200A units had 2 smaller fans while 300 & 400A used a single larger fan along with a larger radiator. More

recently, the single larger fan may be used in the 100 & 200A as well.

Troubleshooting:

1. Confirm that air is exhausting from both the top (top fan)and bottom (bottom fan of units with 2 fans) of the opening in

the right side panel. As the fan(s) are behind the radiator it’s hard to see them to confirm they are turning but perhaps

you can use an inspection mirror. Refer to section for code 403 for troubleshooting defective fans.

!

WARNING!

Fan blades can be moving and accidental contact with a mirror or other inspection devise can cause personal injury

or damage to the machine.

2. Leaving the side panels and cover off, especially the left lower side or the top cover will reduce the air flow. Also if the

radiator fins become clogged with dust it will reduce air flow. Clean the radiator periodically by blowing air into it to clear

dirt from the fins.

259-264 Inverter Over Temperature due to high Ambient.

The CCM measures the ambient temperature where the cooling air enters the louvers on the left side of the front panel. If

an inverter goes over temperature and we have determined that the ambient exceeds 40 deg C we will get one or more of

the high ambient codes, 252-264. The sensor, TS2, is a NTC (Negative Temperature Coefficient) resistor whose resistance

varies with temperature. It is mounted on the inside of the front panel next to the louvers on the left. To access it requires

removing one or more of the inverter modules. If the ambient is high but no inverter is too hot there is no fault.

Possible causes:

• Ambient is too high.
• Cooling fan(s) not operating.
• Disrupted air flow.
• TS2, Ambient temperature sensor, shorted (very unlikely) or otherwise defective.
• Defective Relay board.
• Defective CCM.
• Defective Relay board.

Troubleshooting:

1. If room temperature exceeds 40 deg C, cool the room, or operate the unit at reduced duty cycle or lower current.

2. Confirm that air is exhausting from opening in the right side panel. As the fan(s) are behind the radiator it’s hard to see

them to confirm they are turning but perhaps you can use an inspection mirror. Be careful not to get the mirror or your

hands into the blades. 100 & 200A units have 2 smaller fans, 300 & 400A have one larger one.

3. It is unlikely these high ambient temperature codes would be set before some other temperature related code but just in

case we’ll note that leaving the side panels and cover off, especially the left lower side or the top cover will reduce the air

flow. Also the radiator fins clogged with dust will reduce air.

4. To test TS2 remove J2 from the Relay board and measure the resistance between pins 4 & 6 of the J2 harness connector.

The resistance varies from about 33K ohms at 0 degrees C to about 12K ohms at 20C to 5.3K ohms at 40C.

Advertising
This manual is related to the following products: