Avoid trapped anhydrous, Avoid line traps, Clearing a line trap – Great Plains NP3000A Operator Manual User Manual

Page 110: Ven when completely disconnected. see “ avoid

Advertising
background image

106

NP3000 and NP3000A

Table of Contents

Index

Great Plains Manufacturing, Inc.

407-613M

Table of Contents

Index

2014-04-22

Avoid Trapped Anhydrous

Before servicing anhydrous equipment, or storing it near
untrained individuals, be absolutely certain that there is
no liquid NH

3

trapped in the system, and no NH

3

vapor

present (or only trace amounts).

Follow bleeding and discharge instructions carefully.
Beware of places in the systems where NH

3

can be

trapped.

Avoid Line Traps

Refer to Figure 67
Any two line valves in the system, if both closed with NH

3

present, can trap that ammonia indefinitely. Line valves
include:

tank withdrawal

,

nurse tank hose valve(s)

,

check valves at a disconnected breakaway

,

emergency shut-off valve

,

control valve at rate zero

,

On/Off solenoid valve

, and

aftermarket section valves.

In a properly designed system, segments not open to the
atmosphere are protected by hydrostatic relief valves,
but the operation of such valves only releases a small
portion of the trapped ammonia.

Normal shut-down instructions, after closing the tank
withdrawal valve, are intended to bleed most of the
system NH

3

into the soil. However, there can still be

substantial vapor in the system after that. If shut-down
procedures were not followed, liquid may be present.
If the state of the equipment is not known with certainty
at time of servicing, you need to assume that a closed
valve represents a risk of trapped NH

3

.

The illustration at right depicts a nurse tank hose

in

use, and shut-off while still full of liquid NH

3

. If this hose

is removed to an enclosed space, then opened, it
represents an extreme hazard. Vapor concentrations
could rise to well above IDLH

a

levels in moments.

This example system line segment is equipped with relief
orifice-equipped ball valves

, but that only bleeds the

downstream side of a valve ball, the outlet valve in this
example. See page 107 for information about ball traps.

The downstream side of this system line segment is
equipped with a bleed valve

. The upstream side of

the inlet valve is equipped with a hydrostatic relief
valve

.

If this line segment warms, pressure can rise high
enough to cause periodic releases at the relief valve.
This protects the segment from rupture, but does not
clear the line.

Clearing a Line Trap
To clear a line segment with possible trapped NH

3

:

Move the equipment outdoors.
If calm, wait for wind.
Stand up-wind of the bleed valve.
Point the bleed valve orifice down-wind and away from all

personnel.

If it’s a hose bleed valve, make sure you can set the hose

down with the valve still pointing in a safe direction.

Open the bleed valve very slowly. Once any discharge is

observed, (set any hose down) depart up-wind.

Remain up-wind until the discharge completes.

A10

A11

A12

A10

Figure 66

NH

3

Trapped in Line

31616

Valves Open in Use

Valves Closed with

NH

3

Present

A15

A10

A14

A18

A30

A31

a. IDLH: Immediately Dangerous to Life and Health

A8

A10

A11

A12

Advertising
This manual is related to the following products: