Great Plains NP3000A Operator Manual User Manual

Page 28

Advertising
background image

24

NP3000 and NP3000A

Table of Contents

Index

Great Plains Manufacturing, Inc.

407-613M

Table of Contents

Index

2014-04-22

A28.Pressure Gauge

This gauge reports the pressure of the NH

3

after it

exits the cooler. If line valves are closed, a pressure
reading above zero indicates NH

3

is present

between the emergency shut-off valve

and the

On/Off solenoid valve

(the Control Valve

does not completely close).

Checking the pressure and temperature

against

the chart in the “Using Anhydrous Ammonia
Safely
” manual (407-551M), or in the Raven
AccuFlow™ manual, indicates whether the flowing
NH

3

is in a liquid state.

When valves are open but NH

3

is not flowing, this

gauge normally reads within 5 psi of the nurse tank
pressure gauge

. If they are materially different

at zero flow, one of the gauges may be defective.

When NH

3

is flowing, the pressure reported by this

gauge

is lower than the tank pressure.

A29.Cooler Bleed Valve

This valve is normally closed. It is used to bleed
trapped NH

3

from the cooler system when valves

are closed. It can also be used to accelerate
clearing the cooler system for maintenance.

A30.Control Valve

This is a variable electronic valve controlled by the
SCS 450. It is the primary control point for
application rate. When power is off, this valve
remains at its most recent setting.

This valve has a visible indicator above the valve
ball casing, indicating whether open, closed or in
between.

When commanded to a rate of zero, this valve does
not completely close. Use shut-off valves to
completely stop flow. A full slew from fully open to
minimum takes approximately 9 seconds.

A31.Master Shut-Off Valve

This is the normal control for starting and stopping
total application flow in the field (for turns, etc.). This
component is an open/close solenoid valve
controlled by the “MASTER” switch on the SCS 450.
When power is off, this valve remains at its most
recent setting.

This valve has a visible indicator above the valve
ball casing, indicating whether open or closed.

Operation of this valve is essentially instantaneous.
Its valve ball is equipped with a downstream relief
orifice.

A32.Refrigerant Tap

A small amount of the NH

3

flow is taken at this point

to provide refrigeration at the cooler. There are no
operational items for this fitting.

A33.Refrigerant Line

This tubing passes tapped refrigerant NH

3

to the

cooler. Operator action is to replace this tubing,
a time-dated part, when it reaches the end of its
operating life. See page 115.

A34.Cooler Refrigerant Inlet

Tapped refrigeration flow enters the cooler at this
fitting, and is vaporized to chill the liquid entering at
fitting

. There are no operational items for this

fitting.

A35.Section Control Check Valve

(Section Control Option Only)
This prevents back flow when section shut-off
valves

are off with NH

3

present. There are no

operational items for this fitting.

A36.Section Control Bleed Valve

(Section Control Option Only)
This valve is normally closed. It is used to bleed
trapped NH

3

from the section control system if all

section valves

are closed.

Suffocation, Blinding and Burning Hazards:
See “About Bleed Valves:” on page 38.

A18

A31

A30

A27

A17

A28

Suffocation, Blinding and Burning Hazards:
See “About Bleed Valves:” on page 38.

A22

A39

A39

Advertising
This manual is related to the following products: