Nh3: starting application – Great Plains NP3000A Operator Manual User Manual

Page 66

Advertising
background image

62

NP3000 and NP3000A

Table of Contents

Index

Great Plains Manufacturing, Inc.

407-613M

Table of Contents

Index

2014-04-22

20. Open hose inlet end valve (

, if any - tank

depicted in Figure 36 has no hose valves). Check for
leaks and open valves. Expect NO ammonia odor at
this time.

21. Open hose outlet end valve (

, if any - tank

depicted has no hose valves). Check for leaks. In an
all-Great Plains configuration, if there has been no
odor so far, there should be no odor now, as flow is
blocked at the On/Off valve

(not visible).

Refer to Figure 37
22. At the meter gauges, pressure gauge

should

read within 5 psi

a

of the nurse tank gauge. The flow

divider gauge

should be zero. The temperature

gauge

is likely to be below ambient.

NH

3

: Starting Application

23. Enter the tractor cab.

24. Check the emergency shut-off rope. Make sure you

know where it is. Make sure the rope cannot slip
away. Leave enough slack in the line for uneven
ground.

Refer to Figure 42
25. At the console, set the POWER switch ON.

26. Set the MASTER switch to ON.

27. Set the BOOMS 1 or BOOMS 1,2 & 3 switches on to

ON.

28. Select the desired RATE preset.

29. Lower applicator to operating depth (if not already

lowered) and begin first pass.

NH

3

: Possible Chemical Hazard:

Anhydrous ammonia is now flowing into the ground. Some
routinely escapes to the atmosphere. Check for leaks. Take
action if strong odor is detected or a leak seen. Turn up wind.
Turn off flow. Check gauges from tractor cab. Engage
emergency shut-off valve if a leak is detected.

Minor odor during application is normal, particularly if the
tractor cab is ever down wind of recent passes.

Strong or irritating odor indicates a problem. Conditions
may not be suitable for application (soil too dry, cloddy
and deeply cracked, for example), or there may be a
system problem.

a. This 5 psi correlation is only true under no-flow conditions. When NH

3

application begins, the pressure reading at the cooler gauge

drops, due to the reduced temperature of the cooled fluid, and pressure losses due to flow in plumbing.

Figure 37

Line-Up Gauge Check

31587

A42

A28

A27

A11a

A11b

A31

A28

A42

A27

Figure 38

Typical Application Screen

31585

Advertising
This manual is related to the following products: