S - forcing outputs – Hardy HI 3010 Filler/Dispenser Controller User Manual

Page 130

Advertising
background image

HI-3010 Filler/Dispenser/IBC

114

Service Manual

S - Forcing Outputs

Enter

Diagnostics

STABILITY

TEST

Activate the

test and

review the

results.

These are Opto

isolated solid-state

relays, switching 110-

240 VAC. They will

not work as a dry

contact closure

Contact Hardy

Technical

Support

Verify voltage is

being provided. The

controller will not

supply the switching

voltage

S

No

WARNING: Forcing the output relay may cause
damage or personal injury. Make absolutely sure
you know what the relay is connected to before
activating. If you are unsure, do a physical check
to determine what the selected relay is connected
to BEFORE activating

Yes

PASS

PASS

Use an AC meter to

physically verify

operation

The relay will
activate. Therefore
activating any
machinery attached.

Repeat for

each output

The Force Output function individually
activates each of the 4 Output relays in the
instrument. Useful in pre-startup to determine
that all the relays are connected to the correct
auxiliary devices

Advertising