Jog parameters, About jog parameters, Redient setup menu/selecting target – Hardy HI 3010 Filler/Dispenser Controller User Manual

Page 43: Target window/weight, Target window/percentage, Adjust ingredient 1/jog

Advertising
background image

27

CHAPTER 4
Configuration

FIG. 4-23 INGREDIENT SETUP MENU/SELECTING

TARGET WINDOW/PERCENTAGE

Step 3. Press the Enter button to access the parameter val-

ues.

Step 4. Press the Clear button to clear the entry. Use the

alphanumeric key pad to enter the new Max toler-
ance value either in weight or percentage.

Step 5. Press the Enter button to set the entry.
Step 6. Press the down arrow button so the cursor is in front

of Target Max. (See Fig. 4-24)

FIG. 4-24 TARGET WINDOW/WEIGHT

Step 7. Press the Clear button to clear the entry. Use the

alphanumeric key pad to enter the new Max toler-
ance value either in weight or percentage. (See Fig.
4-25)

FIG. 4-25 TARGET WINDOW/PERCENTAGE

NOTE:

If you set the Target Weight parameter in weight,
when you view the settings in percentage the set
weight is automatically converted to the correct
percentage and vice versa.

Step 8. Press the Enter button to set the entry.
Step 9. Press the down arrow button so the cursor is in front

of Target Min. (See Fig. 4-24)

Step 10. Press the Clear button to clear the entry. Use the

alphanumeric key pad to enter the new Max toler-

ance value either in weight or percentage. (See Fig.
4-25)

Step 11. Press the Enter button to set the entry.
Step 12. Press the Exit button to return to the Adjust Ingredi-

ent 1 Menu. The cursor should be in front of JOG. If
it is not press the up or down arrow until the cursor
is in front of JOG. (See Fig. 4-26)

FIG. 4-26 ADJUST INGREDIENT 1/JOG

Jog Parameters

About Jog Parameters

The Jog is used when a cycle underfills. At the end of a cycle
the system waits to determine the status of a fill/dispense. If
there is an underfill, (i.e. the fill is below the Target Win-
dow) the system waits and then the jog is turned on. The
Filler/Dispenser jogs for a preset period of time for a preset
number of cycles until the fill/dispense is within the Target
Window. If at the end of the jog counts the weight is still not
within the Target Window, you have the option to go through
the jog cycles again. The Jog parameters include the Jog On
Time, the amount of time you want the jog to run for each
jog count. The Jog Count which is the number of times you
want the instrument to go through the jog cycle. The Jog Off
Time is the time you want the jog to be off while the instru-
ment calculates the change in weight to see if the jog
increased the weight so that the fill/dispense is within the
Target Window. To shut OFF the Jog function, set the Jog On
Time to 0.

NOTE:

The Jog settings should be made in conjunction
with the Fast and Slow Fill timers. It is recom-
mended that the AutoPreact be turned on so that
the system can self adjust until you no longer
need a jog during each cycle. If the instrument
goes through the jog sequence for each cycle you
will need to adjust the Fill/Dispense Timers and/
or the Preact.

PARAMETER:JOG ON TIME
RANGE: 00.0-99.9
DEFAULT: 2.50

PARAMETER:JOG COUNT
RANGE: 0-9
DEFAULT: 5